Home » Product List » PVC Insulated Power Cable » Electric Cable
Product Details
Electric Cable
| Model NO.: | yjv |
|---|---|
| Productivity: | 300000m/Month |
| Unit Price: | Negotiable |
| Shipment Terms: | FOB |
| Payment Terms: | L/C,T/T |
| Price Valid Time: | From Oct 20,2011 To Oct 20,2012 |
| Trademark: | HONGYAN |
| Origin: | Shenzhen |
| Certification: | ISO |
| Currency: | AC Cable |
| Voltage: | Ultra-high Voltage Cable |
| Insulation Material: | PE |
| Application: | Power Station |
| Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
(1) Rated voltage Uo/U is 0.6/1 kilovolts.
(2) Maximum rated temperature of cable conductor is 90 0C
(3) Maximum conductor temperature is lower than 2500C when cable is shorted for less than 5 seconds.
(4) Ambient temperature is not lower than 0 0C and its minimum bending radius is as follows when cable is installed:
For single-core calbe-20(D+d), unit: Millimeter
For multi-core cable-15(D+d), unit: Millimeter
The main technical parameters
Calculation condition of the ampacity
Ambient temperature is 25
Coductor working temperature is 90
Soil heat resulted from water migration when it operates continuouly.
Gap between axis of cable and surface of ground is 1000 millimeter when it is laid in ground.
For mint-core cable, gap of axis of cable is 3 times O. D.